Products 12kV-40.5kV C-GIS 12kV SF6 GAS FREE INSULATED C-GIS
12kV SF6 GAS FREE INSULATED C-GIS
AGH-12 type is an environmentally friendly gas-insulated l-enclosed switchgear, which is reliable, safe and stable in operation, and is suitable for use in public and industrial distribution grids, infrastructure projects, railways, llurgy, petrochemicals, piers, ships, drilling platforms, etc., as a means of accepting and distributing electric energy, as well as controlling, protecting and monitoring the electric circuits
Product Features
Environmental protection: adopting N2 as the insulating medium, the primary part is fully sealed structure (air isolation), beautiful appearance, environmental protection and no pollution
Safety and reliability: Complete mechanical and electrical interlocks to ensure operator safety
Small footprint: cabinet width 500mm, cabinet depth 1025mm, small footprint
Efficient operation and maintenance: easy on-site installation, maintenance, expansion and replacement
Operating life: adopting all new composite materials, with a service life of at least 30 years
Intelligent: Intelligent: adopting IT and OT technology, online real-time monitoring
Technical Parameter
12kV   C-GIS Technical specifications
Voltage   level (kV)12
Rated   normal current (A)1250
General requirementInsulation mediumN2 & dry air
Service   ambient temperature(℃)-25 to  +65
Altitude   (m)≤5000
Relative   humidity≤95%
Frequency   (Hz)50/60
Rated   lightning impulse withstand voltageDirectly earthed(kV)75
Across   disconnector(kV)85
Rated   power frequency withstand voltageDirectly earthed(kV)42
Across   disconnector(kV)48
Partial   discharge(pC)1.1Ur≤10
Measurement   of the resistance of Main circuit (μΩ)≤70
ProtectionIndoorIP4X
Outdoor(Non-extensible)IP2X
Tank   with HV partsIP67
Mechanical   impact protectionIK10
Internal   arc ratingAFLR(kA/1s)31.5
N2   & dry airAnnual leakage   rate(year)≤0.01%
Filled   pressure (at 20ºC)  Bar0.02
Minimum   operating pressure (Bar)0
gas   tank ppm(μL/L)≤150
Rated short time withstand current(kA/s)Main electrical circuitRated short-time withstand   current(kA/s)31.5/4
Earth   switchRated short-time withstand   current(kA/s)31.5/4
Earth   circuitRated short-time withstand   current(kA/s)27.4/4
Rated   peak withstand currentMain electrical   circuit (kA)80
Earth   switch (kA)80
Earth   circuit (kA)69.6
Making   and breakingRated short circuit   breaking current (kA)31.5
Rated   short circuit making (peak)current (kA)80
Mechanical   endurance classCircuit Breaker M2(20000)
Disconnectors   and earthing switchesM1(3000)
Size   Wide*Depth*High(mm)500*1025*2330
Executive   standardsIEC 62271-100、IEC 62271-102 、IEC   62271-1、IEC 62271-200、IEC 60255、IEC 60529、IEC 62271-206 
Declaration: This product is a custom class, special requirements can be customised according to customer requirements.